Terminal Operated
|
Between 1 & 2
|
Between 1 & 3
|
Voltage
|
240 VAC
|
120 VAC
|
240 VAC
|
120 VAC
|
Full Load
|
5.5A
|
10.5A
|
2.2 A
|
4.4 A
|
Locked Load
|
22.5 A
|
45 A
|
13.2 A
|
26.5 A
|
Resistive Load
|
6.5A
|
12.5A
|
3.5A
|
6.5A
|
Application
|
Dehumidifier
|
Humidifier
|
Normally Closed
|
Normally Open
|
Heater
|
Fan
|
Design and Test Standard
|
UL 60730-1
|
UL 60730-2-9
|
UL 60730-2-13
|
CAN/CSA-E60730-1:15
|
CAN/CSA-E60730-2-9:15
|
Withstanding Voltage
|
AC 1500 V 1 min or AC 1800 V 1 sec
|
Insulation Resistance
|
Min 100 mΩ at DC 500 V
|
Calibration Point
|
42% RH at room temperature 23 °C ± 2 °C / 74 °F ± 2 °F
|
Mounting
|
Rail 35 mm according to EN 50 022
|
Weight
|
170 gram / 0.375 lb
|
Dimensions
|
101 mm x 57 mm x 55 mm / 3.98″ x 2.24″ x 2.17″
|
Color
|
RAL 7035
|
Electrical Connections
|
3-Pole screw terminal for wires section of .75/4 mm² – AWG 18/12
|
Housing Material
|
PA 6 UL 94-V0
|
Environmental
|
Indoor
|
Control Type
|
Operating Control, Type 1
|
Rated Impulse Voltage
|
2500
|
Hysteresis
|
Approx. 5% RH
|
Sensing Element
|
Synthetic Fiber
|
Operating Temperature
|
10 °C to 40 °C / 50 °F to 104 °F
|
Shipping and Storage Temperature
|
-40 °C to 60 °C / -40 °F to 140 °F
|